Install the mounting frame HTM-RM in the installation opening and clean off dirt and dust. Apply lubricant HTM-SM to the inner surfaces of the frame, and thoroughly lubricate all corners.
Assembly of HTM penetration in rectangular frames HTM-RM with press block HTM-PB
1
2
Route all first-row cables through the frame section. Select NTM modules according to the installation plan, and select inserts according to the cable diameter.
3
Thoroughly lubricate the outer surfaces of the modules and matched inserts (Mount the plug modules together with the core).
4
Fill the sections of the mounting frame with transit modules with cables passing through them, separating adjacent horizontal rows of modules with base plates HTM-OP.
5
Install an HTM-OPF fixing base plate before the last row of modules, followed by an HTM-OP base plate. Move the plates apart within the frame.
6
Place the modules of the last row between the fixing base and base plates. Compress all components with the clamping device HTM-PU or the jack HTM-DMU, and fix with the fixing base plate bolts HTM-OPF.
7
Assemble the HTM-PB press block (corresponding to the width of the mounting frame section), connect its parts with two bolts for 1-2 turns using an Allen key. Thoroughly lubricate the internal and external surfaces of the press-block with HTM-SM lubricant.
8
Insert the press block into the frame over the last support plate. Tighten the bolts with an Allen key, turning them alternately 4-5 turns at a time until both parts of the press-block are tightened, but not fully tightened.
9
Loosen the HTM-OPF bolts one by one to evenly distribute the sealed components. Tighten the press block bolts (no more than 20 Nm). Remove excess lubricant, and check the immobility of the cables in the transit modules.