Need consultation?
Our technical specialists will be glad to help you
Description
At an airport, cable routes link the terminal, control rooms, server rooms, airfield lighting facilities and utility networks, and therefore cross fire barriers many times. Transits HTM close such crossings with a sealing assembly consisting of a mounting frame, transit modules and press-blocks, which prevents fire, smoke and gas from spreading into adjacent rooms.
The requirements for cable installation are the same in the departure hall, in the equipment room and on the apron: it must remain possible to replace the wiring, the sealing must allow additional lines to be laid, and the fire resistance rating of the opening must be no lower than that of the wall or floor. In a transit HTM, the free space in the sealing section is closed with compensation modules or plug modules made of non-combustible elastomer, while transit modules HTM with a core are fitted as spare capacity.
The IET fire resistance rating of transits HTM reaches 150 minutes, as confirmed by TR EAEU 043/2017 and GOST R 53310-2009 certificates — sufficient for facilities with mass occupancy. For low-current and navigation system lines, an EMC (electromagnetic compatibility) version is available with a continuous screen of conductive copper foil: it prevents electromagnetic interference and pulses from passing through the transit. The products comply with GOST 30631-99 for mechanical design groups M25 and M40 and have confirmed seismic resistance of intensity 9 on the MSK-64 scale (GOST 30546).
Main types of transits for airports
Rectangular
A modular assembly in a rectangular mounting frame: transit modules, support and retaining plates, HTM-PB or HTM-PBM press-blocks; cables and pipes with an outer diameter of 3 to 100 mm.
Round modular
An HTM-RMK round mounting frame, an HTM-PBK press-block and transit modules; cables and pipes with an outer diameter of 3 to 100 mm.
Reinforced
Frames with increased wall thickness and rounded corners; typically used in shipbuilding.
Round single
A round mounting frame with an HTM-VO press-block for one cable or pipe with an outer diameter of 3 to 508 mm; no transit modules are used.
Threaded single cable transit HTM-VRO
A threaded entry for a single cable with an outer diameter of 3 to 36 mm; installed without welding.
Cabinet
An HTM-RMSH frame for installation in the wall of a metal control cabinet.
Certificates

IET fire resistance rating up to 150 minutes. Operating temperatures from -60°C to +200°C. Compliance with the requirements of GOST R 53310-2009 and TR EAEU 043/2017

Cable and pipe transits HTM are certified for use in explosive atmospheres and carry the explosion protection marking Ex eb I Mc U, Ex eb IIC Gb U, Ex tb IIIC Db U in accordance with TR CU 012/2011

The designs of the main components of the transit — transit modules HTM and HTM-PB or HTM-PBM press-blocks — are patented

Zavod HERMES products are manufactured in Russia and entered in the Register of Russian Industrial Products (Russian Government Decree No. 719 of 17.07.2015) on the basis of an ST-1 certificate of origin

The design of modular transits HTM provides complete protection against dust and the dynamic action of water jets and complies with the ingress protection rating IP66/IP68

The products are certified in accordance with the Technical Regulations of the Customs Union (TR CU / EAEU) and may be used both in the Russian Federation and in Belarus, Armenia, Kyrgyzstan and Kazakhstan

Components of transits HTM are inspected at every stage of production in accordance with the GOST R ISO 9001:2015 (ISO 9001:2015) quality management system

Compliance with the requirements of STO Gazprom 9001-2018 under the INTERGAZCERT voluntary certification system in respect of the manufacture and sale of fire-resistant explosion-proof cable and pipe transits HTM
Fire resistance ratings
A transit HTM prevents fire, smoke and gas from spreading into adjacent rooms. Different levels of fire resistance are achieved through the design features of the installation rather than a separate product range: all transits hold an IET60 certificate. Fire resistance rating — in accordance with the requirements of GOST R 53310-2009 and TR EAEU 043/2017:
Transits in rectangular frames
IET 60
Single rectangular transit.
IET 90
Asymmetric rectangular transit, structure thickness of at least 150 mm, using a mating frame and PZh120 mineral wool boards.
IET 120
Symmetric rectangular transit, structure thickness of at least 150 mm, using PZh120 mineral wool boards.
IET 150
Symmetric rectangular transit, structure thickness of at least 170 mm, using PZh120 mineral wool boards.
Transits in round frames
IET 60
Single round transit.
IET 90
Asymmetric round transit, structure thickness of at least 150 mm, using a mating frame and PZh120 mineral wool boards.
IET 120
Symmetric round transit, structure thickness of at least 150 mm, using PZh120 mineral wool boards.
IET 150
Symmetric round transit, structure thickness of at least 170 mm, using PZh120 mineral wool boards.
Frequently asked questions
How can I find out the price, availability and delivery times?
Inquiries are sent to the sales department at info@ntm-hermes.com or by phone on +7 (342) 200-88-26. It is worth stating in the inquiry the company and the facility for which the delivery is planned — this speeds up selection and calculation.
Is there a price list for the products?
There is no price list: the cost is calculated individually, depending on the design, materials and scope of supply. First the transit configuration is drawn up, then the managers prepare the calculation.
Are transits HTM resistant to seismic and vibration loads?
Seismic resistance under loads of up to intensity 9 on the MSK-64 scale and compliance with mechanical design groups M25 and M40 according to GOST 30631-99 have been confirmed. Seismic resistance has been confirmed in the “SeismoBezopasnost” voluntary certification system.
Is there a version with protection against electromagnetic interference?
Yes. Transit modules, press-blocks and single entries are available in the EMC (electromagnetic compatibility) version. Transits in the EMC version are fitted with a continuous screen of conductive copper foil. The screen provides continuous screening of the transit at the point of installation, prevents the passage of electromagnetic interference and pulses, maintains electromagnetic compatibility between electrical and electronic devices, and earths the braid of the cables passing through.
Are transits permissible in terminals with mass occupancy?
Yes. The products are used to meet fire safety requirements at civil and industrial facilities: the IET fire resistance rating reaches 150 minutes, and compliance is confirmed by certificates to TR EAEU 043/2017 and GOST R 53310-2009.
Is the solution suitable for entries on the apron and at airfield lighting facilities?
Yes. On the apron and at airfield lighting facilities, transits HTM seal cable entries into buildings, manholes and cable structures, including those located outdoors: the IP66/IP68 ingress protection rating rules out the ingress of water and dust, the operating temperature is from −60 to +200 °C, and the climatic version is UHL1 in accordance with GOST 15150-69.